1.0 KiB
1.0 KiB
# Forced EOC -> Optimize Self-Consumption (discharging)
Initial State: Forced EOC
Target State: Optimize Self-Consumption
Test Procedure
SOCshould be 98% or below- A production deficit is simulated by setting the
Grid setpointto a negative value: -2000W - The system is brought to the
Forced EOCstate usingForce charge nowin the gui. - Wait until the system changes to
Optimize Self-Consumption
Expected Outcome
- The system charges the battery to EOC in the
Forced EOCstate. - charging power decreases as SOC approaches 100%
- the system changes into
Optimize Self-Consumption - the system discharges with 2000W +-100W
Time to forced full chargedisplayed on the gui6d 18h+-1h
Tested Outcome
The system reacted as expected and switched to Optimize Self-Consumption when the battery is fully charged and having
100% SOC. The system is excessively discharging with a power of ~2350W. Time to forced full charge is correctly displayed.