976 B
976 B
# Hold min SOC -> Optimize Self-Consumption
Initial State: Hold min SOC
Target State: Optimize Self-Consumption
Test Procedure
Min SOCis set to slightly lower than the current SOCMin SOCshould be 50% or lowerGrid setpointis set to a negative value -2000W- Wait until the system reaches the
Hold min SOCstate and discharging power falls below 1500W Grid setpointis set to a positive value: 2000W
Expected Outcome
The system first settles into the Hold min SOC state.
As soon as the Grid setpoint is set to positive, the system changes into the Optimize Self-Consumption and
charges with ~2000W.
Tested Outcome
While the system was on Hold min SOC state sitting on around 46% SOC, the Grid setpoint was set to a 2000W, the system
started charging with a power of around 1600W until around 70% SOC, then it started throtteling the charging power.
