711 B
711 B
# Optimize Self-Consumption -> Forced EOC
Initial State: Optimize Self-Consumption
Target State: Forced EOC
Test Procedure
- The system is brought to the
Optimize Self-Consumptionstate by settingMin SOClower than the current SOC Min SOCshould be 50% or lowerForce charge nowis activated on the remote console
Expected Outcome
As soon as Force charge now is activated, the system changes into the Forced EOC state and charges with high power (min. 1000W)
Tested Outcome
The system reacted exactly as expected and switched to Forced EOC state and charged with higher an average power of around 1200w.
