# Optimize Self-Consumption -> Bridge Grid Blackout -> Charge to min SOC -> Hold min SOC
Initial State: Optimize Self-Consumption
Intermediate State: Bridge Grid Blackout
Intermediate State: Charge to min SOC
Target State: Hold min SOC
Test Procedure
SOCshould be 50% or lowermin SOCis set to be at 5% or more below the currentSOCGrid setpointis set to 0W.- a load (min 1000W) is connected to the AC-Out side of the inverter.
- A grid blackout is simulated by manually disconnecting the system from the grid
- The system is left without grid until the
SOCdrops at least 1% belowmin SOC. - The system is connected back to the grid
Expected Outcome
- The system first is in the
Optimize Self-Consumptionstate. - As soon as the grid is disconnected, the system changes into
Bridge Grid Blackout, as visible by the "inverter on" LED on the inverter. - the load must not loose power
- the Venus controller will loose power for a short time and then reboot
- as soon as the Venus has rebooted, the controller should resume in the
Bridge Grid Blackoutstate. (It may transition through theUnknownstate, but it must not stay there for more than 30 seconds) - after the grid has been reconnected (when the
SOCdropped at least 1% belowmin SOC), the inverter synchronizes with the grid and switches back to charger mode ("mains on" LED on the inverter is lit). This should not take longer than 3 minutes. - the Venus controller should then change into the
Charge to min SOCstate. - the system should charge to
min SOCwith at least 1500W - once
min SOCis reached, the controller should switch toHold min SOCand theSOCshould stabilize slightly abovemin SOC. - during the whole procedure the load must never loose power