# Charge to min SOC -> Optimize Self-Consumption
Initial State: Charge to min SOC
Target State: Optimize Self-Consumption
Test Procedure
- The battery is discharged below 20% SOC
Min SOCis set to 20%- A production surplus is simulated by setting the
Grid setpointto a positive value (1200W) - Wait until the
SOCexceeds 22%
Expected Outcome
The system assumes the Charge to min SOC state and charges with high power (~2000W), until it reaches Min SOC.
Once it reaches Min SOC it does the following:
- it changes into the
Optimize Self-Consumptionstate - it continues to charge the battery with an average of 1200W
- charging power does not fluctuate by more than 250W once it has stabilized
Tested Outcome
The system reacted as exactly as expected and switched to Charge to min SOC and charged as fast as possible till reaching the Min SOC.
Once the Min SOC is reached, the battery switches to Optimize Self-Consumption, where the charging power fluctuations don't exceed 200w.