# Charge to min SOC -> Forced EOC
Initial State: Charge to min SOC
Target State: Forced EOC
Test Procedure
- The system is put into the
Charge to min SOCstate by manually setting theMin SOChigher than the currentSOC. Force charge nowis activated on the remote console
Expected Outcome
Any one of the below:
- The system immediately switches to the
Forced EOCstate - The system remains in
Charge to min SOCuntil it reaches theMin SOC, and then switches to theForced EOCstate
Tested Outcome
The system reacted as expected from the second situation and continues the Charge to min SOC until it reaches the
Min SOC, and then switches to the Forced EOC state continuing the same charging pattern, by charging as fast as
possible till reaching the fully charged state.